Rogowski coil current transducer compensation method for harmonic active power error

Risultato della ricerca: Articlepeer review

19 Citazioni (Scopus)

Abstract

In the harmonic active power measurement, the highest uncertainties are generally introduced by the current and voltage transducers. In a previous paper, the authors showed that the current transformer (CT) can introduce significant errors in such measurement, especially if the phase shift between voltage and current is close to ±90°. In such conditionthe errors on harmonic power measurement are mainly due to the CT phase displacement. This paper shows that better results can be achieved with more linear transducers, such as the Rogowski coil current transducers (RCCTs), whose metrological performance in distortedcondition can be improved, by means of a proper compensation method. The proposed method for RCCTs compensation is based on the frequency response and it allows to reduce the errors on harmonic power measurement, also for phase shift close to ±90°. The study is supported by several experimental tests.
Lingua originaleEnglish
pagine (da-a)240-251
Numero di pagine12
RivistaMeasurement
Volume63
Stato di pubblicazionePublished - 2015

All Science Journal Classification (ASJC) codes

  • ???subjectarea.asjc.3100.3105???
  • ???subjectarea.asjc.2200.2208???

Fingerprint

Entra nei temi di ricerca di 'Rogowski coil current transducer compensation method for harmonic active power error'. Insieme formano una fingerprint unica.