Harmonic reduction in CHB 13-level inverters by PAM fundamental-frequency strategy

Risultato della ricerca: Conference contribution

Abstract

In this paper cascaded H-bridges (CHB) 13-level inverters are considered and a particular pulse amplitude modulation (PAM) strategy is introduced to mitigate or eliminate many harmonic components on the output voltage, in order to obtain low Total Harmonic Distortion (THD) factor. This procedure defines different dc voltage sources and sets of six switching angles, depending on an integer parameter q belonging to the close interval I=[11, 15]. The obtained THD doesn't depend on modulation index m. The control of m is made by changing the dc voltage sources that depend linearly on m, while the switching angles remain constant. An investigation about the role of the q parameter on the performances of the CHB 13-level inverter, in terms of mitigated/eliminated harmonics and THD, is shown.
Lingua originaleEnglish
Titolo della pubblicazione ospite8th International Conference on Renewable Energy Research and Applications, ICRERA 2019
Pagine1052-1056
Numero di pagine5
Stato di pubblicazionePublished - 2019

All Science Journal Classification (ASJC) codes

  • Energy Engineering and Power Technology
  • Renewable Energy, Sustainability and the Environment
  • Electrical and Electronic Engineering

Fingerprint Entra nei temi di ricerca di 'Harmonic reduction in CHB 13-level inverters by PAM fundamental-frequency strategy'. Insieme formano una fingerprint unica.