Current and voltage behaviour during a fault in a HV/MV system: Methods and measurements

Maria Luisa Di Silvestre, Gaetano Zizzo, Eleonora Riva Sanseverino, Pons, Luigi Parise, Colella, Montegiglio, Morozova, De Simone, Barresi, Tummolillo, Tommasini, Giuseppe Cafaro, Martirano, Torelli, Roberto Napoli, Parise, Valtorta

Risultato della ricerca: Otherpeer review

11 Citazioni (Scopus)

Abstract

When a single line to ground fault happens on the MV side of a HV/MV system, only a small portion of the fault current is injected into the ground by the ground-grid of the faulty substation. In fact the fault current is distributed between grounding electrodes and MV cables sheaths. In systems with isolated neutral or with resonant earthing this may be sufficient to provide safety from electric shock. Experimental measurements were performed on a real MV distribution network: a real single line to ground fault was made and fault currents were measured in the faulty substation and in four neighbouring substations. In this paper the problem of fault current distribution is introduced, the test system is described and the measurements results are presented.
Lingua originaleEnglish
Pagine404-409
Numero di pagine6
Stato di pubblicazionePublished - 2015

All Science Journal Classification (ASJC) codes

  • Electrical and Electronic Engineering
  • Energy Engineering and Power Technology